Home Products Radio Telemetry RF-Temp 500.4

RF-Temp 500.4

E-mail Print PDF

Industrial Radio

RF-Temp 500.4 provides wireless temperature monitoring over a distance of up to 500m.

Features

  • Master unit - 4 analog (4-20mA) outputs representing a -10 to + 40C range.
  • Sensor units (up to 4 per Master) - 1 digital temperature sensor.
  • Up to 4 Masters can operate together within the same area providing monitoring for up to a total of 16 sensors.
  • Operating distance up to 500m line of site.
  • Repeaters can be used to extend the range.
  • Sensors sample the temperature every 10 minutes & transmit the value to the Master if there is a change of more than 0.5C.
  • If the temperature remains constant, then the value is transmitted every 30 minutes.
  • 4-20mA outputs from the Master are latched @ the last transmitted value.
  • If a value from the sensor is not received for 2 hours, then the Master output channel & LED are switched off.
  • As soon as a value is received again from the sensor, the Master output channel & LED are switched on again.
  • An out of range value of <-20 or >+50C will switch the channel off & flash the LED.
  • Master - low voltage 12 to 28VDC supply.
  • Sensor - internal battery supply, no external wiring required.
  • A low battery condition on the sensor will be indicated by the corresponding channel LED flashing on the controller - the output channel will remain active.
  • Pressing the test button on the sensor causes it to read the temperature & transmit the value every 10 seconds for 5 minutes - used during set up.
  • No programming required.
  • Low power radio that is licence free.
  • For use in non hazardous areas & non safety critical applications.

Specification

  • Sensor units - digital sensor with a usable range of -10 to +40C @ +/-0.5C accuracy.
  • Master outputs - 4-20mA @ 10 bit resolution, requiring external excitation.
  • Range - up to 500m line of site.
  • Sensor supply - internal Alkaline (up to 1 year life), optional Lithium (up to 2 years life).
  • Master power consumption - 50mA @ 24VDC.
  • RF power output - 10dBm @ 433.92MHz - licence free.
  • Master enclosure - ABS, 125x85x55mm, IP65 rating.
  • Sensor enclosure - ABS, 71x71x27mm, wall mount.
  • Master antenna - 1/4 wave whip with SMA male fitting - optional external antenna.
  • Sensor antenna - inbuilt helical.
  • Operating temperature - 10 to 50C.
  • Cable gland  & terminal connection. 

Certification

  • EN 301 489-3
  • EN 300 220-3.
  • EN 300 489.
  • EN 60950.
  • CEPT 70-03 Recommendation.
  • R&TTE complience 1999/5/EC/Directive.
  • Low Voltage Directive (LVD) 2006/95/EC.

 

Attachments:
Download this file (RF-Temp 500.4.pdf)RF-Temp 500.4 pdf[ ]78 Kb
Last Updated on Friday, 20 May 2011 15:06  

paypal logo